點F3短路時的IkAT按11.1.4.1條計算。
11.1.3.1 對稱短路電流初始值I〃k
在計算如圖22所示的非網(wǎng)狀電源饋電的短路電流I〃k時,總的短路電流 I〃k等于各支路電流的代數(shù)和,即:
(55)
![](http://192.168.1.17:8000/UploadFiles/UploadFiles/2009324105719335.jpg)
11.1.3.2 短路電流峰值ip、對稱開斷電流Ib和穩(wěn)態(tài)短路電流Ik如若干電源向短路 點饋電時,三相短路的短路電流峰值ip和開斷電流Ib分別等于各支路的電流ip和Ib 之和。
圖22中點F短路,有:
ip=ipPSU+ipT+ipM+… (56)
上一頁 [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18] [19] [20] [21] [22] [23] [24] [25] [26] [27] [28] [29] [30] [31] [32] [33] [34] [35] [36] [37] [38] [39] [40] [41] [42] [43] [44] [45] [46] [47] [48] [49] [50] [51] [52] [53] [54] [55] [56] [57] [58] [59] [60] [61] 下一頁 |