對(duì)于極功率PrM<1MW的高壓電動(dòng)機(jī):
XM=0.989 ZM時(shí),RM / XM =0.15;
有連接電纜的低壓電動(dòng)機(jī)組:
XM =0.922 ZM 時(shí),RM / XM =0.42。
靜止變頻器驅(qū)動(dòng)的電動(dòng)機(jī)按異步電動(dòng)機(jī)處理,它的阻抗仍按式(34)計(jì)算,式中 各符號(hào)的意義是:
ZM--按式(34)算出的阻抗;
UrM--靜止變頻變壓器電網(wǎng)側(cè)額定電壓或無變壓器時(shí)的靜止變頻器的額定電 壓;
IrM--靜止變頻變壓器電網(wǎng)側(cè)額定電流,或無變壓器時(shí)靜止變頻器的額定電 流;
ILR/IrM--堵轉(zhuǎn)電流與額定電流之比,其值等于“3”,XM=0.995ZM時(shí), RM/XM=0.10。
10.3.2.6 直接與系統(tǒng)連接的發(fā)電機(jī)阻抗
發(fā)電機(jī)不經(jīng)變壓器直接與電網(wǎng)相連,在計(jì)算三相對(duì)稱短路電流初始值時(shí),應(yīng)按 式(35)計(jì)算發(fā)電機(jī)的正序阻抗:
(35)
式中:KG為校正系數(shù),按式(36)計(jì)算如下:
(36)
上一頁(yè) [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18] [19] [20] [21] [22] [23] [24] [25] [26] [27] [28] [29] [30] [31] [32] [33] [34] [35] [36] [37] [38] [39] [40] [41] [42] [43] [44] [45] [46] [47] [48] [49] [50] [51] [52] [53] [54] [55] [56] [57] [58] [59] [60] [61] 下一頁(yè) |