附錄一 諧振容量計算
發(fā)生n次諧波諧振的電容器容量,按下面近似計算式計算
(附1.1)
式中Qcx--發(fā)生n次諧波諧振的電容器容量(Mvar);
Sd--電容器裝置安裝處的母線短路容量(MV·A);
n--諧波次數(shù),即諧振頻率與電網(wǎng)基波頻率之比;
A--電容器裝置每相感抗(XL)與每相容抗(Xc)的比值,
即 A=XL/Xc
附錄二 電容器組投入電網(wǎng)時的涌流計算
一、單組電容器投入時涌流的計算
附圖2.1 單組電容器涌流計算值電路圖
L0-網(wǎng)絡(luò)每相等值電感;L-串聯(lián)電抗器和接線每相電感;
C-電容器組每相電容;DL-斷路器
上一頁 [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18] [19] [20] [21] [22] [23] [24] [25] [26] [27] [28] [29] [30] [31] [32] [33] [34] [35] [36] [37] [38] [39] [40] [41] [42] [43] [44] [45] [46] [47] [48] [49] [50] [51] [52] [53] [54] [55] [56] [57] [58] [59] [60] [61] [62] [63] [64] [65] [66] [67] [68] [69] [70] [71] [72] [73] [74] [75] [76] [77] [78] [79] [80] [81] [82] [83] 下一頁 |