2 承受短路的能力的驗(yàn)證
2.1 承受短路的耐熱能力
2.1.1 概述
變壓器承受短路的耐熱能力應(yīng)根據(jù)計(jì)算驗(yàn)證。
2.1.2 雙繞組變壓器對(duì)稱短路電流I值
三相變壓器對(duì)稱短路電流有效值按下式計(jì)算:
![](http://192.168.1.17:8000/UploadFiles/UploadFiles/2009318114218254.jpg)
式中 I--對(duì)稱短路電流,kA;
ZS--系統(tǒng)阻抗,每相歐姆;
US--系統(tǒng)額定電壓;
S--系統(tǒng)短路表觀容量,MVA。
U和Zt按以下規(guī)定:
a.對(duì)于主分接
U為所考慮的繞組的額定電壓UN,以kV表示。
Zt為折算到所考慮繞組的變壓器的短路阻抗,按下式計(jì)算:
![](http://192.168.1.17:8000/UploadFiles/UploadFiles/200931811438830.jpg)
式中 Zt--短路阻抗,每相歐姆;
US--折算到參考溫度時(shí)額定電流下的阻抗電壓,以百分?jǐn)?shù)表示;
SN--變壓器的額定容量,MVA。
b.除主分接外的其他分接
U為所考慮繞組在相應(yīng)分接的分接電壓(kV)。
上一頁(yè) [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18] [19] [20] [21] [22] [23] [24] [25] [26] [27] [28] [29] [30] [31] [32] [33] [34] [35] [36] [37] [38] [39] [40] [41] [42] [43] [44] [45] [46] [47] [48] [49] [50] [51] [52] [53] [54] [55] [56] [57] [58] [59] [60] [61] [62] [63] [64] [65] [66] [67] [68] [69] [70] [71] [72] [73] [74] [75] [76] [77] [78] [79] [80] [81] [82] [83] [84] [85] [86] [87] [88] [89] [90] [91] [92] 下一頁(yè) |